What storage technology is used?

PMVFUPS01 guarantees the necessary energy by accumulating it in capacitors, thus avoiding the use of batteries which require maintenance. _____________________________________________________________________ Other information on this topic Visit the website page dedicated to Backup power supply for interface protection units.

How long does it take to recharge PMVFUPS01?

A maximum time of 15s is required to fully charge the storage capacitors. The output voltage is present only when the charge is completed. It must be considered that the recharge is required at the very first switch on as well. _____________________________________________________________________ Other information on this topic Visit the website page dedicated to Backup power [...]

By |2021-06-21T15:17:41+02:00May 5th, 2021|, , , , , |Comments Off on How long does it take to recharge PMVFUPS01?

How to choose the interface and back-up switches to be coupled to PMVFUPS01?

PMVFUPS01 accumulates enough energy (200Ws) to correctly drive PMVF series interface protection, a BF or B series contactor by LOVATO Electric acting as an interface switch and the shunt release of the backup. The selection of the right contactor according to the AC3 power is suggested on PMVFUPS01 user’s manual. In case of third party [...]

By |2021-06-21T15:17:54+02:00May 5th, 2021|, , , , , |Comments Off on How to choose the interface and back-up switches to be coupled to PMVFUPS01?