The line contactor must be sized in AC-3 category with a current greater or equal to the motor full load current (FLC).
Example
- Motor rated current = 28 A
- Soft starter rated current ≥ 28A AC-3 (e.g. ADXL0030600 à 30A)
- Line contactor ≥ 28A AC-3 (e.g. BF3200A230 à 32A AC-3)
________________________________________________________________