In the ROGOWSKI COILS DIGITAL MULTIMETER kits (DGM611R …) how long is the cable between the multimeter and the Rogowski coils?

The cable is two meters long. _______________________________________ Other information on this topic Take a look to the Metering instruments and current transformers and to the dedicated brochure. Make sure to visit em.lovatoelectric.com 

By |2021-06-21T17:13:05+02:00June 21st, 2021|, , |Comments Off on In the ROGOWSKI COILS DIGITAL MULTIMETER kits (DGM611R …) how long is the cable between the multimeter and the Rogowski coils?

How the measurement accuracy is warranted in DIGITAL MULTIMETER WITH ROGOWSKI COILS kit?

In the kit made by the multimeter and the three Rogowski coils the calibration certificate elaborated by the calibration process is included. the certificate is associated with the kit by reporting the serial number. _______________________________________ Other information on this topic Take a look to the Metering instruments and current transformers and to the dedicated brochure. Make sure to [...]

By |2021-06-21T16:51:02+02:00June 21st, 2021|, , |Comments Off on How the measurement accuracy is warranted in DIGITAL MULTIMETER WITH ROGOWSKI COILS kit?

Why the coils are sold as a kit with the multimeter?

The output signal of a Rogowski coil must be processed in order to amplify, shift and filter it. Those operations are in charge of DMG611R… multimeter. The level of signal processing depends on each single coil piece, thus it is necessary that each measuring current input of DMG611R… is coupled and calibrated to get the [...]

By |2021-06-21T16:51:32+02:00June 21st, 2021|, , |Comments Off on Why the coils are sold as a kit with the multimeter?

When is a measurement solution with Rogowski coils current inputs convenient?

Two fundamental differences arise between a traditional split-core current transformer and a Rogowski coil, even if both of them are current transducers: the Rogowski coil is flexible and deformable, while a CT is rigid and non-deformable;  considering the same primary current, the Rogowski coil occupies less space. For those reasons, the solution with Rogowski coils [...]

By |2021-06-21T16:51:53+02:00June 21st, 2021|, |Comments Off on When is a measurement solution with Rogowski coils current inputs convenient?

How does the minimum measurement current indicated for the measuring device influence the energy data?

The accuracy of the measuring instruments is guaranteed within a range of current values indicated by the manufacturer. In particular, below the minimum value the instrument is no longer required to measure with the prescribed accuracy. It is therefore necessary to pay attention to situations in which the current absorbed by the loads varies frequently [...]

By |2021-06-17T14:46:24+02:00April 26th, 2021|, , |Comments Off on How does the minimum measurement current indicated for the measuring device influence the energy data?

Rogowski coils: how often do they need to be recalibrated?

All kits are calibrated during the testing process by LOVATO Electric and come with the relevant calibration report. Kits don't need calibration during their life in the electric plant. _____________________________ Other information on this topic Take a look to the Metering instruments and current transformers and to the dedicated brochure. Make sure to visit em.lovatoelectric.com 

By |2021-06-17T14:45:46+02:00February 9th, 2021|, |Comments Off on Rogowski coils: how often do they need to be recalibrated?

Which are the pre-requisites to be considered to take the most of EXCGLA01 gateway data logger?

The devices to be monitored must be equipped with RS485 or ethernet ports; EXCGLA01 must be connected to the local network (LAN), possibly by a static IP address or a dynamic IP assigned by a DHCP server where EXCGLA01 MAC address is coupled to a known IP; The IP address assigned to EXCGLA01 must be [...]

By |2021-06-17T14:45:23+02:00January 25th, 2021|, |Comments Off on Which are the pre-requisites to be considered to take the most of EXCGLA01 gateway data logger?

How to upgrade the software running on EXCGLA01?

In case of new software releases of the applications loaded in EXCGLA01, the upgrade files should be downloaded from www.lovatoelectric.com in the product page. Run the following steps in sequence. Unzip the archive file and verify the presence of the following folder: a. “updateV1.0_V2.1” folder. 2) Copy “src” and “Lovato” folders and 2 files in [...]

By |2021-06-17T14:44:57+02:00January 5th, 2021|, |Comments Off on How to upgrade the software running on EXCGLA01?

Is the connection to a remote server mandatory to work with EXCGLA01?

When the connection to a remote server is not possible or not required, EXCGLA01 offers the built-in web interface by which all data can be downloaded to Excel or CSV files. _______________________________________________________________ Other information on this topic Take a look to the Gateway data logger and to the energy management brochures. Make sure to visit em.lovatoelectric.com  Watch our video tutorials [...]

By |2021-06-17T14:44:45+02:00January 5th, 2021|, |Comments Off on Is the connection to a remote server mandatory to work with EXCGLA01?